BS ISO 13379-2:2015 gives procedures to implement data-driven monitoring and diagnostic methods to facilitate the work of analysis carried out by specialist staff typically located in a monitoring centre.

Although some of the steps are embedded in existing tools, it is essential to be aware of the following steps for optimum use:
  • selection of the asset, the critical failures and the available process parameters;
  • data cleaning and resampling;
  • model development;
  • model initialization and tuning;
  • model performance evaluation;
  • diagnostics process.
The implementation of these steps does not require a thorough knowledge of the statistical methods.

It does require the competence first to build the training models and then to carry out monitoring and diagnostics processes.

The training in data-driven monitoring is carried out on equipment that is exhibiting normal behaviour.

In that case, the principle of fault detection is to compare observed data to estimated data. A difference (called residuals) between an observed and expected values of the parameters reveals the presence of an anomaly, which can be related either to equipment or instrument.

The training in data-driven diagnosis is carried out both on equipment that is exhibiting normal behaviour and failures. The principle of the method is not to detect the deviation of a parameter but to identify a fault by comparison of the observed situation to the faults learnt during the training phase.

The technique usually applied is pattern recognition followed by pattern classification.

Data can be available from the data historian of the distributed control system (DCS) or from specialized monitoring systems.


Cross References:
ISO 13372
ISO 13379-1
ISO 17359:2011


Replaces BS ISO 13379:2003 which remains current

All current amendments available at time of purchase are included with the purchase of this document.
 

Document History

  1. BS ISO 13379-2:2015

    👀 currently
    viewing


    Condition monitoring and diagnostics of machines. Data interpretation and diagnostics techniques-Data-driven applications

    • Most Recent
  2. BS ISO 13379:2003


    Condition monitoring and diagnostics of machines. General guidelines on data interpretation and diagnostics techniques

    • Historical Version